Description
Corrosion Inhibitor for Water Systems having unique formulation with highly concentrated liquid cooling treatment compound with indicator, ferrous & Non ferrous corrosion inhibitors, antiscalants , dispersant and buffer solution of non carbonate.Usefull for use in high or low temperature closed cooling water systems for the prevention of corrosion and scale formation in internal combustion engines, compressors, chiller system and DG sets. Protects all metals including cast iron, mild steels and copper. Recommended ppm levels are easily controlled by standered RXSOL test kit Nitrite / Chloride.
Technical Bulletin
ROCCOR NB RXSOL WITH INDICATOR.
RXSOL-40-4034-025
Scale and corrosion inhibitor with indicator
Chilled Closed Circuit Water Treatment
Introduction:-
RXSOL-40-4034-025 is a unique formulation with organic Corrosion Inhibitors , Anti-Scalant for use in closed cooling water systems , for preventing corrosion and scale Formation in Internal combustion engines, compressor cooling system, DG -set at high or low temperature.It is a concentrated liquid ,also used as a corrosion inhibitor ( Protects all the metals including cast iron , mild steel , copper etc)
Note:-The stable oxide film that is formed by RXSOL-40-4034-025 prevents corrosion caused by electrolytic action between dissimilar metals used in the system .RXSOL-40-4034-025 has been field tested and found to have no detrimental effects on non metallic substances such as seals, glands, packing, hoses, gaskets etc., normally used in these system .
Application – SDG*Sets:- Internal combustion engines closed circuit cooling system compressor cooling system RXSOL-40-4034-025 incorporates superior corrosion inhibitors to prevent corrosion works by free of scale deposits.
Advantages:-
1. Prolong the life of equipment by keeping scale and corrosion free. Since RXSOL-40-4034-025 is alkaline and so will suppress acid corrosion, which would otherwise result in corrosion damage such as pitting. However, the alkalinity control is such that even if the product is accidentally overdosed, the pH of the water will remain within limits. The metals which would be affected by extremes of alkalinity or acidity are protected.
2. Improves generating cooling efficiency by maintaining a clean heat transfer
3. Corrosion protection by using superior corrosion inhibitor.
4. Reduced maintenance and down time.
6. Friendly with Metals (Like steel, Copper, Aluminum, all alloys) & Non-metal (Rubber, Hoses, Gasket etc.)
Note:- In cases where systems are contaminated with oil and/or scale they should be cleaned before starting to apply RXSOL-40-4034-025 .There are suitable RX BRAND products to carry out the cleaning. Degreasing should be carried out using RXSOL-16-1005-025 and descaling by using RXSOL-16-1008-025.
Specification:-
Colour |
Pink |
Sp. Gravity |
1.2 to 1.3 |
pH |
Alkaline ( 11.3 – 11.8 ) |
Odour |
Odourless |
Boiling Point |
100 degre C |
Solubility |
100% in water |
Freezing Point |
17 degree C |
Handling:- RXSOL-40-4034-025 is an alkaline product & should be handled like other chemical Avoid contact with Eyes, Skin ,in case of contact ,wash with copious amounts of water immediately.
General Recommendation |
||||||
Nitrite (as PPM NO2) |
0 |
100-200 |
300-600 |
700-900 |
1100-1300 |
1440-2400 |
RXSOL-40-4034-025/1000L |
13.0 |
11.3 |
8-10 |
5-7 |
1.5-3.5 |
0 |
Method Of Use:-
1. Properly clean the system with water and alkaline liquid , if necessary.
2. Add 0 .15-1.5 % of RXSOL-40-4034-025 in system or recommended Nitrite level 1400 – 2500 ppm can be measured and controlled by any standard RXSOL test kit for Nitrite, Chloride test also helps to detect excess contamination to maintain accepted levels .when the product is dosed as recommended limit By buffering action of 1. Properly clean the system with water and alkaline liquid , if necessary.
2. Add 0 .15-1.5 % of RXSOL-40-4034-025 in system or recommended Nitrite level 1400 – 2500 ppm can be measured and controlled by any standard RXSOL test kit for Nitrite, Chloride test also helps to detect excess contamination to maintain accepted levels .when the product is dosed as recommended limit By buffering action of RXSOL-40-4034-025 , pH should be maintained between 8.3 and 10 by the treatment.
Note:- Initial dosage for an untreated system is 9 litres of RXSOL-40-4034-025 / 1000 litres of untreated distilled water.This will bring the treatment up to the minimum level of 1000 ppm nitrite. For best result and prolonged engine life add RXSOL-40-4034-025 every 500 -6500 km. or 250 to 300 hours of running time or every 2 month interval .pH should be maintained between 8.3 and 10 by the treatment.
Label
Industrial applications: Corrosion inhibitor for recalculating cooling water treatment
Put on appropriate personal protective equipment (sea section 8). Eating, drinking and smoking should be prohibited in areas where this material is handled, stored and processed Workers should be wash hands and face before eating, drinking and smoking. Do not get in eyes or on skin or clothing. Do not breathe vapor or mist. Do not ingest. If during normal se the material presents or respiratory hazard. Use only with adequate ventilation or wear appropriate respirator. Keep in the original container or an approved alternative made from a compatible, kept tightly closed when not in use. Keep away from acids. Empty containers again product residue and can be hazardous.
Do not reuse container
No action shall be taken involving any personal risk or without suitable training. Evacuate surrounding areas. Keep unnecessary and unprotected personnel from entering do not touch or walk through spilled material. Avoid breathing vapor or mist provide adequate ventilation Wear appropriate respirator when ventilation is inadequate put on appropriate personal protective equipment
LABEL PROPERTY
product property
Odour……………………. Odourless
Appearance………………….. pink
pH………………………………….. 8.5 – 9.5 at 100 % concentration
Boiling point ………………………….> 100 °C at 760 mm /Hg
Vapour pressure …………………..not known
Vapour density ………………………not applicable
Freezing point …………………………<0 °C at 760 mm/Hg
Completely soluble in water
Specific gravity (water=1) .....................1.10